Alarm Annunciator Panel2018-10-23T14:23:48+08:00

Alarm Annunciator Panel AAP-10

The AAP-10 Alarm Annunciator Panel provides visual and audible alarm indications for single or grouped digital inputs.

It is manufactured from universal cells, which can be assembled in an array to provide the number of alarm channels required to a suit individual system configuration.

Each cell of the AAP-10 contains 4 digital inputs, 2 alarm extension relays outputs and up to 4 independently LED illuminated windows of customised colours. Each replaceable alarm lamp assembly has inherent LED redundancy. A maximum of 63 cells plus operator keypad can be set into an array to suit any application.

Additional or standard system functions are configurable using up to 6 external key inputs.

A clear plastic cover with a diffuser sheet protects the alarm transparency within a plastic bezel.

aap-10_4x1_3x5

Supported Alarm Sequences

ANSI/ISA-18.1979 (R1992)

  • A (Auto Reset)
  • M (Manual Reset)
  • F1A (No subsequent Alarm State – Automatic Reset)
  • F2M-1 (No subsequent Alarm Flashing – Manual Reset – Silence Pushbutton)
  • F3A (First Out Flashing and Reset Pushbutton – Automatic Reset)
  • 4 (No lock in)
  • R (Ringback)
  • R-12 (Ringback with Auto Acknowledge)

System Functions

The AAP-10 can be operated with additional functions such as

  • Attended/Unattended Mode
  • Alarm Output Mute
  • Dark and Silent

Applications

The AAP-10 is suitable for industrial applications as well as harsh environments such as the oil and gas industry. The design also allows installations in electrical substations to comply with EMC/EMI requirements as specified in IEC 61850-3.

aap-10_application

Features

  • Modular multi-processor cell based system design
  • Configurable alarm panel size from 4 to 252 with optically isolated inputs
  • Programmable alarm extension relay configuration for each alarm input
  • Alarm grouping through dedicated alarm relay modules
  • Selectable alarm window size and a range of alarm LED colours
  • Printable alarm windows using standard printers
  • Integrated keypad and programmable alarm buzzer
  • Isolated external keypad inputs for remote user interface
  • Additional system functions configurable on external keypad
  • Programmable Boolean alarm grouping
  • Wide range power supply options from 24 Vdc to 140 Vdc and 110/240 Vac
  • Redundant power supply configuration with failure monitoring possible
  • Easy to use AAP Designer Configuration Tool
  • Configuration file download via standard USB port
  • Input and output connectivity via compression type terminals   
  • Panel Mount

Technical Specifications

Alarm Sequences
(ANSI ISA 18.1)
A – Automatic Reset
M – Manual Reset
F1A – Auto 1st Reset, No Subsequent Alarm
F2M-1 – Manual 1st Reset, No Subsequent Alarm
F3A – Auto 1st Reset, 1st Out, Flash
R – Ringback, Audible Output
R12 – Ringback with Auto Acknowledge
4 – No Lock in
Operational Modes Attended/Unattended, Sleep, Dark and Silent
Alarm Input Channels 5 kV optically isolated 24 Vdc to 110 Vdc
Logical alarm grouping with Boolean AND/OR across cells
Normal or inverted logic state
Filter Time 1 to 3000 milli-seconds
Delay Time 0 to 6000 milli-seconds
Alarm Display 2 parallel LED’s per lamp inserted in socket
White – 5000 mcd
Green – 3000 mcd
Red – 1600 mcd
Amber – 1800 mcd
Visible area 30 x 30 mm to 65 x 65 mm in various configurations
Audible Alarm 2.9 kHz @98 db/30 cm
Power Supply
idle = no inputs or outputs are active
max load = all inputs and outputs are active
Wide Range
DC 18 – 74 V
DC 36 – 144 V
AC 90 to 260 V
Keypad Controller
1.50/2.40 Watts
4 Channel Input LED Module
0.25/1.00 Watts
4 Channel Relay Module
0.25/0.70 Watts
Operating Temperature -10 °C to +55 °C
Mounting Panel Mount

 

Compliances

(Tested to IEC 61850-3 standard)

Immunity  
IEC 61000-4-2 Electrostatic discharge Test Level 3
IEC 61000-4-3 Radiated radio-frequency, electromagnetic field immunity Test Level 3
IEC 61000-4-4 Electrical fast transient, burst immunity Test Level 4
IEC 61000-4-5 Surge Immunity Test Level 3
IEC 61000-4-6 Immunity to conducted disturbance induced by radio-frequency fields Test Level 3
IEC 61000-4-16 Immunity to conducted asymmetric disturbances Test Level 4
IEC 61000-4-17 Immunity to ripple on DC input ports Test Level 3
IEC 61000-4-18 Immunity to damped oscillatory waves Test Level 3
IEC 61000-4-29 Voltage dips, short interruptions and voltage variations immunity test

 

Emission  
CISPR 22 Conducted disturbances, disturbance voltage Limit Class A
CISPR 22 Radiated disturbance, electric field strength Limit Class A

 

Safety  
IEC 60255-27 Clearance, creepage 5kV

 

System Components

aap-10_led_module 4 Channel input LED module with 2 alarm extension relays
aap-10_keypad_module Keypad Controller with 6 external key inputs, 1 alarm relay and USB port
aap-10_alarm_module Alarm module with 4 relays

 

eNode Designer

The eNode Designer is an easy to use system engineering tool for on-site system setup and configuration. It also allows the user to print all alarm labels and to manage projects with a single or a large number of AAP-10 devices.

aap-10_screenshot

Go to eNode Designer download page

Contact Us 🗪
close slider

Have a question?

Feel free to let us know if you have any queries related to our products or engineering services.

* indicates mandatory field

Name *

Phone Number *

Email *

Company Name *

Company Address

Subject *

Message *

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.